Eaton Power Xpert 9395 three-phase UPS
Rating
1001,910 kVA/kW
Phase
3PH
Models
11
Lifecycle
Full

Overview

The Eaton Power Xpert 9395 is a three-phase UPS series for critical loads, data centres, healthcare, industrial and infrastructure. We specify the right configuration from the Power Xpert 9395 line, supply it, and install it turnkey across Canada. We carry every major brand, so we can compare the Power Xpert 9395 against the alternatives on price, footprint and lead time.

THREE PHASE POWER PATH3 PHASE INPUT480 V or 208 V feedRECTIFIERAC to DCDC BUSregulatedINVERTERDC to clean ACCRITICAL LOADracks, plant, imagingBATTERYon the DC busSTATIC BYPASSmaintenance and overload pathDouble conversion: the load stays on the inverter, so an outage produces no transfer gap.

How a three phase double conversion UPS carries the load, and where the bypass sits.

Power Xpert 9395 models

The orderable configurations we supply and service:

ModelRatingPhase / VoltagePart numberStatus
Eaton Power Xpert 9395 225kVA2053ph in/out 480/400V,Current
Eaton Power Xpert 9395 250kVA2283ph in/out 480/400V,Current
Eaton Power Xpert 9395 275kVA2503ph in/out 480/400V,Current
Eaton Power Xpert 9395 450kVA4103ph in/out 480/400V,Current
Eaton Power Xpert 9395 500kVA4503ph in/out 480/400V,Current
Eaton Power Xpert 9395 550kVA5013ph in/out 480/400V,Current
Eaton Power Xpert 9395 650kVA5923ph in/out 480/400V,Current
Eaton Power Xpert 9395 750kVA6833ph in/out 480/400V,Current
Eaton Power Xpert 9395 825kVA7513ph in/out 480/400V,Current
Eaton Power Xpert 9395 1000kVA9103ph in/out 480/400V,Current
Eaton Power Xpert 9395 1100kVA10013ph in/out 480/400V,Current

Specifications

Phase3ph in/out
Voltage480/400V
Models11
StatusCurrent

Efficiency, footprint & paralleling

Double-conversion efficiency on the Power Xpert 9395 is above 94%, rising to 99% with Energy Saver System. Eaton rates it the smallest footprint and lowest weight in its class, “50 to 60 percent less than competitive units”; an 825 kVA N+1 system is about 39 sq ft against a competitor’s ~125 sq ft. Input current distortion stays under 5% with no input filter (which eases generator sizing), and it carries leading power-factor loads to 0.9 without de-rating. Powerware Hot Sync wireless paralleling scales to 4 distributed modules, or 32 through the System Bypass Module, with load-sharing held under 3% and no system-level single point of failure; at or below 50% load the power modules behave as N+1 without a second UPS. An Easy Capacity Test stresses the full power train at full load with no external load bank.

In the field

Hurricane Electric deployed a pair of 550 kVA Power Xpert 9395 units with ESS in its 208,000 sq ft Fremont 2 data centre. Eaton reports the units held 99% efficiency even at roughly 60% site load, ESS keeps efficiency high where lightly-loaded double conversion would sag, with lower utility and cooling cost and a footprint that preserved rentable colocation space. After about three years the operator bought ten more 9395 units. We supply, install and maintain the 9395 the same way, on a service plan if you want one.

Sources: Eaton, Power Xpert 9395 brochure (9395FXA) and Hurricane Electric case study (CS151001EN). Figures are Eaton’s published specifications.

Sizing, redundancy and custom builds

We engineer the solution: load and growth analysis, redundancy (N, N+1, 2N), runtime and battery sizing, paralleling and switchgear, and custom configurations where the standard catalogue doesn't fit. Because we supply every major brand, the Power Xpert 9395 is one option we weigh on its merits, not the only answer.

Supply, install and lifecycle

We deliver, install and commission the system on site (coordinated with your electrical contractor), then keep it running with preventive maintenance, battery replacement and emergency support, including Power Xpert 9395 units that are out of warranty or discontinued by the manufacturer.

Common questions

Can you replace an old or discontinued unit with a different brand?

Yes, that's most of what we do. Send the model and part number you have (any brand, even end-of-life) and we cross-reference an equivalent that matches the load and footprint. If the original is back-ordered, we propose an in-stock unit that ships sooner.

Do you replace just the batteries, or the whole UPS?

Whichever is the better value. A battery replacement (sometimes with an added cabinet for more runtime) often restores full protection at a fraction of a new system. We need your exact model and variant to quote it accurately.

What are the lead times?

It depends on the model and stock. When the original has a long lead time, we usually propose an equivalent we can ship sooner so the load isn't left exposed. Tell us your timeline in the quote.

Do you install it, and across Canada?

Yes, we supply, install and commission the system anywhere in Canada, coordinated with your electrician, and maintain it afterward: preventive maintenance, batteries, emergency support and remote monitoring, on a single unit or a multi-site fleet.

Can you quote a complete system, not just the UPS?

Yes, UPS, power distribution, racks, batteries and the installation in one quote, coordinated with your electrical contractor.

Request a Eaton Power Xpert 9395 quote

Tell us the application and we will come back within one business day, sizing, the right system, install and a price. Three-phase installs usually need a licensed electrician, so let us know if you have one.