Eaton · Power Xpert 9395
The Eaton Power Xpert 9395 is a large double-conversion three-phase UPS rated 225 to 1,100 kVA at 480 V or 400 V.

Eaton lists the Power Xpert 9395 in its current 9395 family, alongside the higher-efficiency 9395P and the 9395XC and 9395XR. For service, Eaton's table keeps the original 9395 frames (275 to 1,100 kVA) in full support until best efforts begin in 2033, or 2043 under its extension program.
Sources, checked October 3, 2026: Eaton, 9395 UPS family page; Eaton, UPS End of Service Life master table PL161010EN (rev. May 29, 2026).
2:09. On an Eaton 9395 the daily list is short: uncluttered surroundings, front intakes and top exhaust free, room within environment, Online lamp lit. Monthly: monitor the parameters; the filters sit behind the front panels, so the filter check belongs to the visit. The cabinet is not to be operated with doors open or panels removed (p. 248), and battery plants are replaced in planned outages. Source: Eaton's Power Xpert 9395 manual 164201764 Rev 18.
0:00 What does a maintenance visit check on an Eaton 9395? What does a maintenance visit check on an Eaton 9395? The daily list is short, the monthly list adds two items, and the cabinet itself belongs to a scheduled visit.
0:11 What is on you daily? What is on you daily? Keep the surroundings uncluttered, keep the front intakes and the top exhaust free, keep the room within its specified environment, and confirm the Online lamp.
0:22 And monthly? And monthly? Monitor the system parameters. And check the UPS air filters, located behind the front panels or door, and wash or replace them as necessary, exactly as the manual assigns to the user.
0:35 What does the visit look for? What does the visit look for? The wear parts: fans, capacitors and the battery string, covered before they become alarms. For the 9395 family, Eaton's lifecycle schedule puts the AC capacitors outside the modules at about year 7 and the DC capacitors inside the modules at about year 10.
0:56 Which batteries does it take? Which batteries does it take? Lead-acid or lithium-ion, and 9395 battery plants are large: replacements are planned outages, matched to the existing cabinet configuration.
1:10 What about the bypass? What about the bypass? A maintenance bypass means the load runs on unconditioned utility power, with no battery backup. And the manual is explicit: the UPS should not be operated with the cabinet doors open or protective panels removed.
1:25 What should you keep between visits? What should you keep between visits? The EVENTS screen: active alarms, notices, commands and a historical log. Photograph the logs before any reset; the order of events is the diagnosis.
1:38 What are the call signs? What are the call signs? The manual's rule: call if an alarm lamp is lit or the Online indicator is not lit. The lamp set also gives you red for an active alarm and yellow for battery or bypass.
1:50 Request a quote If your 9395 is due for a visit, request a quote at threephaseups.ca.
How a three phase double conversion UPS carries the load, and where the bypass sits.
The orderable configurations we supply and service:
| Model | Rating | Phase / Voltage | Part number | Status |
|---|---|---|---|---|
| Eaton Power Xpert 9395 225kVA | 205 kW | 3ph in/out 480/400V | 9395 225/205 | Current |
| Eaton Power Xpert 9395 250kVA | 228 kW | 3ph in/out 480/400V | 9395 250/228 | Current |
| Eaton Power Xpert 9395 275kVA | 250 kW | 3ph in/out 480/400V | 9395 275/250 | Current |
| Eaton Power Xpert 9395 450kVA | 410 kW | 3ph in/out 480/400V | 9395 450/410 | Current |
| Eaton Power Xpert 9395 500kVA | 450 kW | 3ph in/out 480/400V | 9395 500/450 | Current |
| Eaton Power Xpert 9395 550kVA | 501 kW | 3ph in/out 480/400V | 9395 550/501 | Current |
| Eaton Power Xpert 9395 650kVA | 592 kW | 3ph in/out 480/400V | 9395 650/592 | Current |
| Eaton Power Xpert 9395 750kVA | 683 kW | 3ph in/out 480/400V | 9395 750/683 | Current |
| Eaton Power Xpert 9395 825kVA | 751 kW | 3ph in/out 480/400V | 9395 825/751 | Current |
| Eaton Power Xpert 9395 1000kVA | 910 kW | 3ph in/out 480/400V | 9395 1000/910 | Current |
| Eaton Power Xpert 9395 1100kVA | 1001 kW | 3ph in/out 480/400V | 9395 1100/1001 | Current |
Double-conversion efficiency on the Power Xpert 9395 is above 94%, rising to 99% with Energy Saver System. Eaton rates it the smallest footprint and lowest weight in its class, “50 to 60 percent less than competitive units”; an 825 kVA N+1 system is about 39 sq ft against a competitor’s ~125 sq ft. Input current distortion stays under 3.5% with no input filter (which eases generator sizing), and it carries leading power-factor loads to 0.9 without de-rating. Powerware Hot Sync wireless paralleling scales to 4 distributed modules, or 32 through the System Bypass Module, with load-sharing held under 3% and no system-level single point of failure; at or below 50% load the power modules behave as N+1 without a second UPS. An Easy Capacity Test stresses the full power train at full load with no external load bank.
Hurricane Electric deployed a pair of 550 kVA Power Xpert 9395 units with ESS in its 208,000 sq ft Fremont 2 data centre. Eaton's case study reports that the 9395 with ESS exceeded all expectations, providing the highest uptime and efficiency at the lowest possible cost, and the operator names efficiency and total cost of ownership as the deciding factors. After about three years the operator bought ten more 9395 units. We supply, install and maintain the 9395 the same way, on a service plan if you want one.
Sources: Eaton, Power Xpert 9395 brochure (9395FXA) and Hurricane Electric case study (CS151001EN). Figures are Eaton’s published specifications.
Lead-acid or lithium-ion battery options. Battery kits that suit this platform are in the Eaton UPS battery catalogue.
We service the Eaton Power Xpert 9395 across Canada: preventive maintenance, battery replacement and emergency repair, including units the manufacturer no longer supports. We are a Canadian UPS service and supply provider, working on three-phase systems since 2012.
Planned visits and emergency calls are arranged through on-site service for the Eaton Power Xpert 9395.
We engineer the solution: load and growth analysis, redundancy (N, N+1, 2N), runtime and battery sizing, paralleling and switchgear, and custom configurations where the standard catalogue doesn't fit. Because we supply every major brand, the Power Xpert 9395 is one option we weigh on its merits, not the only answer.
The Eaton Power Xpert 9395 is a large double-conversion three-phase UPS rated 225 to 1,100 kVA at 480 V or 400 V.
No. Eaton lists the Power Xpert 9395 in its current 9395 family, alongside the higher-efficiency 9395P and the 9395XC and 9395XR. For service, Eaton's table keeps the original 9395 frames (275 to 1,100 kVA) in full support until best efforts begin in 2033, or 2043 under its extension program.
Lead-acid or lithium-ion battery options.
A Canadian UPS service and supply provider, in business since 2012, services the Eaton Power Xpert 9395 across Canada: preventive maintenance, battery replacement and emergency repair, including discontinued units. Call 1 (438) 881-3363 or email info@threephaseups.ca.
Tell us the application and we reply within 4 business hours with the sizing, the right system, the installation and a written quote. Three-phase installs usually need a licensed electrician, so let us know if you have one.
Brand names are trademarks of their owners and are used only to identify the equipment we service. We are not the manufacturer and are not affiliated with it.