Engineering guide
The Galaxy VL tells you how serious an alarm is before you read it: the alarm status symbol turns blue for informational, yellow for a warning and red for a critical alarm, and any module framed in red on the mimic diagram is inoperable or in alarm. Open the active alarms log, record the message, and call a technician for red alarms or red modules.

The symbol in the top right corner of the display follows the worst active alarm: green for none, blue for informational, yellow for warning, red for critical. Tapping it opens the active alarms log. On a Galaxy VL this is the fastest triage step: blue can usually wait for the next maintenance visit, yellow needs a look the same day, and red needs a technician.
The mimic diagram frames active modules (rectifier, inverter, battery, static bypass switch) in green and inactive ones in black. A module framed in red is inoperable or in an alarm condition. Combine the two views: the alarms log tells you what, the mimic tells you where in the power path. If the display fails, the manual notes that the operation mode can still be read on status LEDs behind the front panel, which is a job for qualified staff.
The Logs screen holds the latest 100 events, newest first. For a fault investigation, the manual describes exporting a UPS report from Maintenance > UPS report to a USB device; on the VL the USB port is on the system level controller behind the front door, so let the technician pull it. Keep the event list photographed until then, because a log can be cleared from the same screen.
Readings on the status screens are not lab-grade: the manual asks for a tolerance of ±1% on voltages and ±3% on power and currents when comparing the display with a power analyzer.
Some informational items are maintenance reminders rather than faults, for example the air filter reminder, which is reset once the filter has been replaced. Batteries are the other planned item: a VL battery plant ages whatever the display says, and replacement batteries for Schneider three-phase systems are easier to source before a string fails than after.
For planned work on a modular VL, Schneider Galaxy maintenance visits cover modules, fans, filters and batteries; the modular vs monolithic guide explains what changes for service on a modular frame.
At least one informational alarm is present, often a reminder such as the air filter. Open the active alarms log to read it.
The manual says that module is inoperable or in an alarm condition. Note which module it is and call for service.
The Logs screen shows the latest 100 events, with the newest at the top.
The manual gives a tolerance of ±1% on voltages and ±3% on power and currents for the display values.
The manual describes the export, but the USB port sits on the system level controller behind the front door, so leave it to the technician.
Sources, checked October 4, 2026:
Fill this in and your own mail client opens with everything already written out. Nothing is sent from this site.
Brand names are trademarks of their owners and are used only to identify the equipment we service. We are not the manufacturer and are not affiliated with it.