Toshiba G9000 fault codes explained

On a Toshiba G9000, codes starting with UA are alarms and codes starting with UF are failures, according to section 8 of Toshiba's installation and operation manual 61480-018. The last two digits tell you the weight: 00 to 49 is a Major failure, where the load goes to the static bypass line, and 50 to 99 is a Minor one, where the UPS keeps running but the cause still has to be found. The tables below give the manual's meaning and guidance for the codes operators meet most.

Worker in a safety vest installing a switchgear cabinet in an electrical room

Key facts

How a G9000 code is built

The second letter separates alarms (UA) from failures (UF). The first digit after the letters points to the circuit: 0 for the rectifier, 1 for the DC circuit, 2 for the inverter, 3 for control, 4 for the bypass system and 8 for alarms. The last two digits give the weight: 00 to 49 is Major, 50 to 99 is Minor.

The display shows the code, a status message and a guidance line. Note all three, with the time, before anyone resets the unit; the manual asks for that record first.

Input and bypass alarms

CodeMessage on the displayWhat the manual saysWhat to do
UA801AC INPUT VOLTAGE OUT OF RANGEInput line voltage out of the specified range.Check the input power source.
UA802AC INPUT FREQUENCY OUT OF RANGEInput line frequency out of the specified range.Check the input power source; a generator may be running.
UA803AC INPUT PHASE ROTATION ERRORInput conductors not in the proper phase sequence.Have an electrician check the input wiring.
UA812BYPASS VOLTAGE OUT OF RANGEBypass line voltage out of the specified range.Check the bypass input.
UA813BYPASS PHASE ROTATION ERRORBypass conductors not in the proper phase sequence.Have an electrician check the bypass wiring.
UA814BYPASS FREQUENCY OUT OF RANGEBypass line frequency out of the specified range.Check the bypass input.
UA815TRANSFER PROHIBITEDTransfer to bypass unavailable because the bypass is abnormal.Postpone any planned transfer.
UA835TRANSFER PROHIBITEDThe UPS could not transfer because the bypass source has an abnormality.Check the bypass source.

These alarms report the supply. Check for a utility event, a generator start or recent upstream work. A phase rotation error after electrical work is corrected at the wiring, by an electrician.

Overload alarms

CodeMessage on the displayWhat the manual saysWhat to do
UA805INVERTER OVERLOADOutput load current above 105% of rated current.Reduce the load (DECREASE LOAD).
UA806INVERTER OVERLOADOutput load current above 110% of rated current.Reduce the load.
UA807INVERTER OVERLOADOutput load current above 125% of rated current.Reduce the load.
UA808INVERTER OVERLOADOutput load current above 150% of rated current.Reduce the load now.
UA810INVERTER OVERLOADShort-time overcurrent detected during inverter operation.Reduce the load.
UA870BALANCER OVERLOADNeutral point voltage unbalance detected.Check how single-phase loads are spread across phases.
UF258LOAD ABNORMALLoad transferred for overload more than 4 times within 5 minutes.Call a technician.

The four inverter overload codes step up from 105% to 150% of rated current, so the code itself tells you how far over the unit is. Shed non-critical load first. UF258 means four transfers in five minutes: leave the load on bypass and call.

Battery codes

CodeMessage on the displayWhat the manual saysWhat to do
UA824CB2 OPENThe battery circuit breaker (CB2) is open.Confirm whether it was opened for work; the guidance is TURN ON CB2.
UA834BATTERY DEPLETED/AC OUT STOPPEDBattery voltage has reached the depleted level (Major).Restore the input supply; call a technician.
UF157BATTERY OVERTEMPERATUREOvertemperature detected at the batteries.Check the battery room temperature (CHECK BATTERY).
UF158BATTERY LIQUID LOWLow battery electrolyte level.Have the battery string inspected (CHECK BATTERY).
UF162BATTERY ABNORMALFailure found by the battery self-check.Call a technician.
UF163BATTERY VOLTAGE ABNORMALBattery voltage is abnormal.Call a technician.

Overtemperature and self-check failures are usually the first sign that a string is aging. Our Toshiba UPS service team tests the string under load before deciding on replacement, and matching blocks for G9000 cabinets are in the replacement battery catalogue.

Breakers, emergency stop and external signals

CodeMessage on the displayWhat the manual saysWhat to do
UA817EMERGENCY STOP ACTIVATEDEmergency stop activated by the EPO switch or an external contact.Find what triggered the EPO before any restart.
UA822TRANSFER PROHIBITEDNo transfer to bypass because the generator-operation signal says a backup generator is running.Expected while on generator.
UA831EMERGENCY BYPASS SWITCH ONThe emergency bypass switch has been turned on.Check whether work is under way; call a technician.
UA83352L OPENThe load circuit breaker (52L) is turned off.Confirm whether it was opened on purpose.
UA890EXTERNAL ALARMAn external alarm relay turned on.Check the equipment wired to that input.
UF42052L OPERATION ERRORLoad breaker 52L opened during inverter operation (Major).Call a technician (guidance: CHECK 52L).

Failures that need a technician

CodeMessage on the displayWhat the manual saysWhat to do
UF102DC OVERVOLTAGEDC voltage above the overvoltage level (Major).Call a technician.
UF103DC UNDERVOLTAGEDC voltage below the undervoltage level (Major).Call a technician.
UF201INVERTER OVERVOLTAGEOutput overvoltage detected (Major).Call a technician.
UF203INVERTER OVERCURRENTInverter overcurrent detected (Major).Call a technician.
UF213OVERTEMPHeatsink temperature above its thermal setting (Major).Call a technician; check the room cooling.
UF214COOLING FAN ABNORMALThermal relay protection activated (Major).Call a technician.
UF301UPS CONTROL CIRCUIT ERRORAD reference has an abnormal value (Major).Call a technician.
UF40152S ABNORMALContactor 52S failed to close (Major).Call a technician.

Every UF code with CALL SERVICE ENGINEER is a technician job. Keep the cabinet closed, leave the load where the UPS put it, and pass on the record of codes and times.

Related pages

Common questions

What is the difference between UA and UF on a Toshiba G9000?

UA codes are alarms and UF codes are failures, per the code key in manual 61480-018.

How do I know if a G9000 failure is Major?

Look at the last two digits: 00 to 49 is Major, with the load moved to the static bypass; 50 to 99 is Minor.

What does UA805 INVERTER OVERLOAD mean?

The output load current has exceeded 105% of the rated current. Reduce the load.

Why does the G9000 refuse to transfer to bypass on generator?

UA822 appears when the generator-operation signal says a backup generator is running; the transfer is blocked on purpose.

What does UF213 OVERTEMP mean?

The heatsink temperature exceeded its thermal setting. It is a Major failure: call a technician and check the room cooling.