Delta Ultron HPH alarm messages explained

The Delta Ultron HPH 60 to 120 kVA shows its alarms as plain messages on the LCD, such as OVERLOAD or BATTERY LOW SHUTDOWN. Chapter 11 of Delta's HPH user manual gives the possible cause and solution for each. A handful have an operator fix: reduce the load below 95%, improve ventilation, or reset a frozen LCD. Most say to contact service personnel, and the manual adds that an alarm which persists once causes are ruled out goes to the dealer or customer service.

Man carrying a box down a long aisle of dark green server cabinets

Key facts

How the HPH reports alarms

The message appears on the LCD, and the manual's troubleshooting table pairs each message with a cause and a solution. Record the exact message and the time before anything is reset.

Load messages

Message on the displayWhat the manual saysWhat to do
OVERLOADThe UPS is overloaded.Remove unnecessary loads to bring the total below 95%.
INDUSTRY PROTECTIn industrial mode, the output has an overcurrent.Check that the output and the loads are normal.
SHORT CIRCUITThe output has a short circuit.Call service personnel.

Delta asks for the total load to come back below 95% of capacity, not just under 100%, so leave a margin when you shed.

Temperature and fan messages

Message on the displayWhat the manual saysWhat to do
OVER TEMPERATUREThe UPS temperature is too high.Improve ventilation, reduce load, check from outside that fans run; filter cleaning is maintenance work.
PFC AMBIENT OVER TEMP. FAILThe UPS temperature is too high (PFC ambient).Same checks as OVER TEMPERATURE.
FAN FAILFans are damaged or stuck.Call service personnel.

Supply, battery and display messages

Message on the displayWhat the manual saysWhat to do
INPUT PHASE SEQUENCE FAILInput phase sequence is wrong.Have an electrician check the input phase sequence.
BYPASS PHASE SEQUENCE FAILBypass phase sequence is wrong.Have an electrician check the bypass phase sequence.
BATTERY REVERSEDBatteries are connected in reverse.Do not restart; have the battery polarity checked.
BATTERY LOW SHUTDOWNBattery voltage is low.Let the batteries charge once mains power is back.
LCD error or no responseLCD fail, communication fail or noise interference.Press UP and DOWN together for about 5 seconds to reset the LCD; call service if it persists.

Internal faults that need a technician

Message on the displayWhat the manual saysWhat to do
INVERTER FAILInverter is damaged.Call service personnel.
OUTPUT FUSE FAILOutput fuse is broken.Call service personnel.
INPUT FUSE FAILInput fuse is broken.Call service personnel.
AUX POWER FAILAuxiliary power is damaged.Call service personnel.
BYPASS SCR SHORT FAILBypass SCR driver damaged or SCR shorted.Call service personnel.
INVERTER SOFT START FAILInverter detection abnormal or driver damaged.Call service personnel.
INNER COMMUNICATION FAILInner communication cable not well connected.Call service personnel.
DC BUS HIGH SHUTDOWNOutput abnormality or internal fault.Call service personnel.

Fuses, SCRs, the inverter and internal cabling are all inside the cabinet, so these are service calls. Our Delta Ultron service visits start from the alarm record, and when the external batteries are the cause, battery string replacement is planned around the load.

Related pages

Common questions

What does OVERLOAD mean on a Delta HPH?

The UPS is overloaded. Remove unnecessary loads until the total is below 95% of capacity.

How do I reset a frozen HPH display?

Press the UP and DOWN keys together for about 5 seconds. If the error remains, call service personnel.

What does INDUSTRY PROTECT mean?

In industrial mode, the output has an overcurrent. Check that the output and loads are normal.

What should I do on BATTERY REVERSED?

The batteries are connected in reverse. Do not restart; have the polarity checked.

What if an HPH alarm stays after all checks?

The manual says to contact the local dealer or customer service once all possible causes are eliminated.