N+1 vs 2N: what you can maintain without shutting the load down

Redundancy decides what can be serviced with the load still protected. Internal N+1 lets one module be swapped on line, but shared frame parts still need a bypass window. Parallel N+1 lets one whole UPS be isolated. 2N lets a complete system, batteries and switchgear included, come out of service while the other carries the load.

Glass-walled corridor along a data centre with yellow walls

Key facts

Internal N+1: one module more than the load needs

In a modular frame, N+1 means one extra power module. XPC puts numbers on it for the M90U-80: with 20 kW modules, the N+1 capacity is 60 kW, one module below the full frame, and the modules are hot-swappable without risk to the critical load. Schneider Electric's Galaxy VS allows power modules to be inserted or removed in any operation mode on units with the Live Swap label, and ABB describes its DPA modules as operating completely independently of each other.

The limit is the shared part of the frame: static switch, controls, bypass. Work there needs a bypass window, and on a Galaxy VS the batteries are not available as backup while the UPS is in maintenance bypass.

Parallel N+1: one unit more than the load needs

Several complete UPS units share the load, with one more than needed. Manufacturers publish the limits: up to 4 or 8 Toshiba G9000 units depending on the rating, up to 8 Mitsubishi 9900B units, up to six ABB SG Series units, and Delta's Modulon DPH up to 8 units. One unit can be isolated for maintenance while the others carry the load. The parallel system still has shared behaviour: Vertiv's NX manual lists a System Transfer message, when the whole paralleled system transfers to bypass at the same time.

2N: two complete systems

Two independent systems each carry the full load, feeding dual-corded equipment or a static transfer switch. One complete system, its batteries and its switchgear included, can be taken out of service while the other carries the load.

What can be serviced with the load still protected

What needs workInternal N+1 (modular frame)Parallel N+1 (separate units)2N (two systems)
One power moduleOn line, where the frame supports hot swapOn line, inside the affected unitOn line
One complete UPSBypass windowThat unit is isolated, the others carry the loadOn line
Shared static switch, controls or bypassBypass windowBypass window for the shared partsOn line
Output switchgearShutdown or external bypassShutdown or external bypassOn line, one side at a time

Planning maintenance around redundancy

Our data centre UPS service plans each visit around the redundancy the site actually has, and strings for redundant battery banks are matched through the data centre battery program. Definitions of N, N+1 and 2N: UPS redundancy explained.

Related pages

Common questions

Can an N+1 UPS be maintained without a shutdown?

Partly. A redundant module or unit can be serviced on line, but parts shared by the whole system, such as the static switch, controls or output switchgear, still need a bypass window or a shutdown.

Is the load protected during maintenance bypass?

It is powered by the utility without battery backup. Schneider Electric's Galaxy VS manual states the batteries are not available as an alternate power source in maintenance bypass.

What does 2N add over N+1?

A complete second system. Each one carries the full load, so a whole system, batteries and switchgear included, can be maintained while the other runs.

How many UPS units can run in parallel?

It depends on the model: up to 4 or 8 Toshiba G9000 units depending on the rating, up to 8 Mitsubishi 9900B units, up to six ABB SG Series units.

Does modular N+1 need any shutdown at all?

For module work, often not. For the shared frame parts, yes: plan a bypass window and keep it short.