Service by brand
Vertiv's Liebert APM2 user manual says the UPS system, battery included, requires periodic service and maintenance to ensure long service life, and it spells out what that means: battery terminal connections inspected and tightened at least once a year, screws tightened at least once a year, air filters cleaned or replaced about every two months in normal conditions, and the battery kept between 20 °C and 25 °C. Our preventive maintenance visit on Liebert systems follows that list and adds the readings that show what is ageing.

The manual also states that service and maintenance must be performed by trained personnel only.
You get a written report with every reading next to the previous visit, and what to budget for next.
Our Liebert visits are part of the Liebert maintenance contracts we run across Canada, and a site can request a plan for several units through the preventive plan request.
Vertiv's manual puts a number on the cost of heat: if the average battery temperature rises from 25 °C to 35 °C, the service life of the battery is reduced by 50%. A battery room that runs warm is the first thing we flag. The APM2's periodic battery self-test can be set from 30 to 360 days; it confirms the battery is active, while the block-by-block readings of a maintenance visit show which block is ageing first.
The visit applies to APM2, EXM, EXM2, EXS, EXL S1, ITA2, NX and NXL, with the item list adjusted to each model's own manual.
A maintenance contract fixes the visit schedule and the report format for one site or a fleet: UPS maintenance contracts. New large Vertiv systems are started up by Vertiv to keep the factory warranty in place; our contracts cover the years after that.
Same-day service in Montreal, Quebec City, Toronto and Ottawa; 24 to 48 hours elsewhere in Canada. We reply and quote within 4 business hours. Tell us the brand, the model and the symptom or the visit you need, and the quote comes back with the scope and the date.
All Liebert service: Vertiv and Liebert UPS service. Other brands: Eaton preventive maintenance and APC preventive maintenance.
Vertiv's APM2 manual asks for yearly checks of the battery terminals and the screws, and air filters every two months in normal conditions. Most sites book one full visit a year and add a filter check in between, or a second visit in dusty rooms.
The APM2 manual says to clean or replace them once every two months under normal conditions, and more often in dusty or unclean rooms. The filters can be replaced while the UPS is operating.
The APM2 manual asks for 20 °C to 25 °C. At an average of 35 °C instead of 25 °C, the service life of the battery is reduced by 50%.
No. The self-test, settable from 30 to 360 days, confirms the battery is active. It does not measure each block, check terminal torque or find a hot connection.
Yes, with the same visit, adjusted to the model's own manual, while parts and batteries can be sourced.
Sources, checked October 4, 2026: